UFC 4-021-02

UFC 4-021-02, Electronic Security Systems, is the U.S. Department of Defense Unified Facilities Criteria document for designing electronic security systems (ESS): intrusion detection, access control, video surveillance, data transmission and the command and control equipment that ties them together. The current edition is dated 28 July 2025. Its preparing activity is the Naval Facilities Engineering Systems Command, with the U.S. Army Corps of Engineers and the Air Force Civil Engineer Center, and it supersedes the edition of 1 October 2013. It is approved for public release. 1 An earlier Navy version, UFC 4-021-02NF of 27 September 2006, replaced the Navy design manual DM-13.02, Commercial Intrusion Detection Systems, of September 1986. 2

The document says its purpose is to give uniform requirements and guidance for designing ESS in support of DoD physical security programs. It does not itself create a requirement for an ESS; the requirement comes from DoD or Service policy, installation needs or users, and the design assumes risk assessments are already complete. It applies to all construction, renovation or repair projects that include an ESS, and names the Service offices with authority over ESS designs. 1

Chapter 3 covers intrusion detection. It defines an IDS as sensors connected through intrusion panels and a network to a central system, divides sensors into interior, exterior perimeter and exterior wide-area categories, and uses four performance metrics: probability of detection, nuisance alarm rate, false alarm rate and vulnerability to defeat. Sensors must reach a probability of detection of at least 95 percent, with a goal of 99 percent; interior sensors are limited to three nuisance alarms and one false alarm a month, and exterior perimeter sensors to three and one a day. The document deliberately says no more about vulnerability to defeat because of security classification concerns. It requires UL 634 Level 2 high security switches for SCIFs and special access program facilities, and treats "balanced magnetic switch" as a legacy term for the high security switch. 1 Later chapters cover access control, video surveillance, data transmission, integration, the design process, coordination with other disciplines, and system testing and documentation. 1

Source · UFC 4-021-02, Electronic Security Systems (opens in a new tab) · U.S. Department of Defense, Unified Facilities Criteria (WBDG)

References

  1. UFC 4-021-02, Electronic Security Systems (opens in a new tab) · U.S. Department of Defense, Unified Facilities Criteria (WBDG) · July 28, 2025 ↩ ↩ ↩ ↩