A balanced magnetic switch (BMS) is a door or window position sensor built to resist the magnet attack that defeats an ordinary magnetic contact. The Navy design manual DM-13.02, Commercial Intrusion Detection Systems (September 1986), explains the problem: because a plain magnetic switch is held in its normal position by a magnet, an intruder can defeat it by placing a strong magnet near the switch so its contacts do not change when the door opens. For that reason the manual calls the balanced (or biased) magnetic switch the only acceptable type for most DoD applications, and requires tamper protection on surface-mounted models for high-security use; recessed models are protected because the door frame must be attacked first. 12

The manual describes three designs and how each can still be beaten. A biased switch uses one reed switch with a biasing magnet that the actuator magnet offsets; an expert could defeat it with a single magnet of the right size and polarity in the right place. A balanced switch adds an unbiased reed that should operate only when a second magnet appears; it needs adjustment at installation and periodic checks, and could be defeated by an expert moving a magnet into place in step with the door from inside the protected area. A preadjusted balanced switch uses three biased reeds of opposed polarity, an optional tamper reed, a matched three-magnet housing and built-in steel, so it needs no field adjustment. 1

Current DoD design criteria treat the name as historical. UFC 4-021-02 (28 July 2025) defines the balanced magnetic switch as a legacy term superseded by high security switch (HSS): a door position switch held in a balanced or centre position by interacting magnetic fields when not in alarm. It requires UL 634 Level 2 high security switches for SCIFs and special access program facilities, describing Level 2 as meeting additional requirements for performance, tampering, nuisance alarms and reliability, and allows Level 1 or Level 2 elsewhere. 3 The intelligence community's SCIF technical specification likewise requires UL 634 Level II switches on SCIF perimeter doors together with a motion sensor. 4 An Intertek notice on the UL 634 revision effective 27 March 2016 lists compromise tests for high security magnetic switches, including attempts to hold the switch with wire or thin strips, substitution with a portable test magnet in several orientations, and a magnetised steel plate slid between switch and magnet. 5

Source · NAVFAC DM-13.02, Commercial Intrusion Detection Systems: magnetic switches (opens in a new tab) · Naval Facilities Engineering Command (third-party transcription, Integrated Publishing)

References

  1. NAVFAC DM-13.02, Commercial Intrusion Detection Systems: magnetic switches (opens in a new tab) · Naval Facilities Engineering Command (third-party transcription, Integrated Publishing) · Design manual of September 1986. ↩ ↩
  2. UFC 4-021-02NF, Electronic Security Systems (opens in a new tab) · U.S. Department of Defense, Unified Facilities Criteria (WBDG archive) · September 27, 2006 · Cover records that it replaces Navy Design Manual 13.02 of September 1986. ↩
  3. UFC 4-021-02, Electronic Security Systems (opens in a new tab) · U.S. Department of Defense, Unified Facilities Criteria (WBDG) · July 28, 2025 ↩
  4. Technical Specifications for Construction and Management of Sensitive Compartmented Information Facilities, Version 1.5.1 (opens in a new tab) · National Counterintelligence and Security Center (archived copy, Internet Archive) · July 26, 2021 · Chapter 2 response times and Chapter 7 intrusion detection systems. ↩
  5. SUN - UL 634, Connectors and Switches for Use with Burglar-Alarm Systems (opens in a new tab) · Intertek · Standards update notice; revised requirements effective 27 March 2016. ↩

Research articles

See what connects to it on the map of ideas →

See also