Abstract

When enterprise IT is compromised, can an industrial operator disconnect its operational technology (OT) network and keep the physical process running safely? This article uses islanding for deliberate separation from enterprise IT and the internet with continued local operation, leaving open at most an explicitly approved and verified outbound-only data link. Five cases illustrate different outcomes. Colonial Pipeline chose a preventive shutdown and later restored limited service. Ukrainian distribution utilities recovered power through manual operation after the December 2015 attacks, while analysis of malware linked to Kyiv’s 2016 outage illustrates the potential for automated interference inside a control network. Norsk Hydro contained ransomware and reported uneven production effects. At Maersk, a disconnected identity server survived NotPetya and aided recovery. The Purdue model, IEC 62443 standards and NIST guidance help map dependencies and select controls. CISA recommends exercising response decisions and receives incident reports under applicable TSA directives. A cut is viable when the operator can demonstrate that local control, safety functions, dependencies and staffing support the proposed operating mode for a specified time.

What islanding means here

In electric power engineering, an island is a portion of a power system that is electrically separated from the rest of the grid and remains energized by local sources. The National Renewable Energy Laboratory describes both intentional and unintentional islands in its report on distributed generation interconnection. Protective separation can also de-energize equipment. In an analysis of the malware associated with the December 2016 Kyiv outage, Dragos modeled a scenario in which protective operations would isolate a substation and take it offline. That scenario describes a possible consequence of the malware. Whether it occurred during the incident is unverified, and it provides no evidence of continued local supply.12

Here, islanding means deliberately separating an OT network from enterprise IT and the internet during an incident while continuing to operate the physical process locally. In that definition, separation describes the network and continuity describes the process. The cut removes every path that originates on the enterprise side and every interactive path, such as remote access, management, update and support connections. A hardware-enforced one-way link that only exports data from the OT side may stay open if the response plan explicitly approves that flow and the operator verifies that nothing can return across it; NIST describes such a gateway as permitting authorized traffic in one direction only. An operator can also use isolation to support a controlled shutdown. If operators regain local control after losing a supervisory system, or recover a backup that happened to be offline, those are distinct outcomes. Recovery from the Ukrainian distribution attacks of December 2015 extended into 2016 in some locations as utilities worked without their normal supervisory control and data acquisition (SCADA) environments. That episode is separate from the December 2016 transmission outage.324

For the operator, what matters is what the remaining equipment and people can actually do. A communications link can be isolated while local control continues at normal output, proceeds at reduced capacity, or supports a managed stop. The proposed mode determines what belongs inside the separation boundary. A local console that can still display a reading may be sufficient for one decision. Another decision may require a current reading from an independent instrument, the ability to change the process, and an operator authorized to act. An inventory of connections has to be read alongside the conditions for safe operation.56

The Purdue model and its limits

The Purdue model descends from a reference model for computer-integrated manufacturing prepared by the CIM Reference Model Committee of the International Purdue Workshop on Industrial Computer Systems and edited by Theodore J. Williams. NIST traces ISA-95’s enterprise-control integration model to the Purdue reference model. The levels run from the physical process and basic control through supervisory control and site operations to enterprise functions. In NIST’s examples, a demilitarized zone (DMZ) mediates exchanges between the control and enterprise networks. NIST suggests considering architectures such as Purdue, ISA-95 or three-tier industrial IoT, individually or in combination. It also describes grouping assets by criteria including management authority, trust, criticality, data flow and location.75

NIST recommends limiting firewall rules to communications between adjacent levels, tiers or zones. In a Purdue architecture, its example prevents direct communication from enterprise devices at Level 4 to devices at supervisory, basic control and process Levels 2, 1 and 0. The example supplies a starting point for checking direct paths. Establishing trust still requires knowing which services and devices can initiate or authorize an action. A diagram placing a workstation on the control side does not establish where it gets its credentials, or whether operators can log in after a restart while disconnected. The retained network may include Levels 0–2 and any Level 3 services essential to the selected mode. Determine which identity, DNS, time, licensing and vendor-access dependencies exist and trace each one along its actual path.5

The December 2015 investigation illustrates the value of tracing the path. E-ISAC and SANS describe spearphishing in the corporate environment and use of remote-access connections into the control environment. Their investigation found that the virtual private network (VPN) connections from business to control networks appeared to lack two-factor authentication. A nominal boundary between networks leaves an operator with the practical question of which sessions it permits and what privileges those sessions convey.3

CISA’s report on a separate natural gas compression facility describes initial access to IT via a spearphishing link, followed by a pivot into OT. Ransomware affected Windows assets on both networks. Operators suffered a partial loss of view, but control remained available. A separate control office retained operational visibility and lacked the equipment to control the process. The operator chose a controlled shutdown, which took about four hours to transition into. Other compression facilities also shut down because of pipeline transmission dependencies, and the pipeline asset was down for approximately two days. Availability of control at one console, usable visibility at another, and the ability of the pipeline asset to continue operating were three distinct questions.6

Dependencies can also run from OT to IT. The Congressional Research Service (CRS) gives an example in which an OT system reports pipeline shipments to an IT system used for customer scheduling and billing. This is a dependency to test at a particular operator. Ask what the loss of reporting means for loading, acceptance of new orders and later reconciliation. Those functions may have different tolerances for delay. Record which deliveries can proceed using verified local records and whether the business can account for those deliveries after systems return.8

Five incidents and their separation outcomes

CaseDateWho initiated separationWhat function was lostWhat process continued or returned
Ukrainian distribution utilitiesDecember 23, 2015Attackers opened breakers through the utilities’ control systems.3About 225,000 customers across three utilities lost power. Damage to operator systems and communications constrained remote control.3Manual operations restored power. Dragos reports loss of automated control lasting into 2016 in some locations.32
Ukrenergo transmissionDecember 17–18, 2016Switching during an attack caused the outage. ESET assessed that Industroyer was likely used.94The Pivnichna outage interrupted supply to part of Kyiv and its surroundings for more than an hour.4Supply returned after the outage. The toolkit gives no basis for inferring local supply from an energized island.4
MaerskJune 27, 2017A prior power outage had disconnected a Ghana domain controller. Maersk also disconnected network links during containment.10The attack disrupted IT and transport and logistics operations.1110Terminal staff used manual workarounds. The surviving controller supplied a copy of directory data for IT recovery.10
Norsk HydroMarch 2019Hydro isolated plants and operations after discovery of the attack.1213Several Extruded Solutions plants temporarily stopped, with Hydro reporting lost access to production systems.12Energy and Bauxite & Alumina reported normal production. Primary Metal produced at normal levels with more manual operation.12
Colonial PipelineMay 7, 2021Colonial ordered a pipeline shutdown to contain the incident.14Pipeline operations initially halted system-wide.14Some laterals ran manually before the May 12 full-system restart began.15

Cutting on suspicion: Colonial Pipeline, 2021

On May 7, 2021, an employee found a ransom note in Colonial’s IT network just before 5:00 a.m. Eastern Daylight Time (EDT), according to CEO Joseph Blount’s written Senate testimony. The employee notified the control center’s operations supervisor, who issued the stop-work order. Employees began the shutdown at approximately 5:55 a.m. EDT and confirmed it was complete by 6:10 a.m. EDT. The roughly fifteen minutes describes execution of the shutdown after discovery and the stop order. Blount testified that the system carried products including gasoline, diesel, aviation fuel and home heating oil. The BBC reported Colonial’s estimate that the pipeline supplied about 45 percent of the East Coast’s gasoline, diesel and jet fuel.1416

Blount described the company’s assessment that an attacker used a legacy VPN profile that was intended to be out of use. In the hearing he said the profile had single-factor authentication. The written testimony describes an existing incident response process and standing authority to stop work when safety is at risk. The immediate reason for the stop order was to contain the attack and prevent spread into OT if it had yet to reach that network. Blount said Colonial then scanned its systems for malware and other indicators of compromise. GAO, citing a DHS and FBI advisory, reported that there were no indications as of May 12 that the affected operational systems had been breached. The public record supports reading the decision as containment under uncertainty. It leaves Colonial’s verification capability and the effectiveness of particular segmentation controls unestablished.141718

Colonial reported manual operation of some laterals before it initiated the system restart on May 12 at approximately 5 p.m. Eastern time. It announced that deliveries had begun in all markets on May 13 and that the pipeline was transporting refined products at normal levels on May 17. These milestones measure different things: partial delivery, initiation of a restart, reach across markets, and transport at normal levels. The company described safety assessments as part of starting up. For continuity planning, tracking those stages separately makes room for the period in which a service is available to some customers or for some uses while the system is still recovering.15

The Department of Justice reported that Colonial paid approximately 75 bitcoin on May 8, 2021. The BBC reported a payment valued at about $4.4 million and attributed to The Wall Street Journal the account that the supplied decryptor did not allow an immediate restart. On June 7, DOJ announced a seizure of 63.7 bitcoin, valued at about $2.3 million at seizure. It said the FBI held the private key to the address holding those funds. How the key was obtained and the ultimate disposition of the seized funds remain unverified here.1916

Manual recovery: Ukraine, 2015

E-ISAC and SANS report that at Kyivoblenergo, starting at about 3:35 p.m. local time on December 23, 2015, seven 110 kV and twenty-three 35 kV substations were disconnected for three hours. That is one distribution utility’s reported time and scope. The investigation reports that the incidents at three utilities were executed within thirty minutes of one another and affected about 225,000 customers in aggregate. The interval describes the coordination of the incidents. The report attributes the switching to direct interaction by the attackers with the control systems, while destructive activity compromised systems operators needed for recovery.3

The report describes damage to operator workstations and communications equipment that impeded remote control. It also describes thousands of calls to one utility’s call center that kept customers from reporting outages. The report discusses a possible broader purpose of interference with the operators’ response. Customer call blocking is the documented effect. Local manual operation supported restoration of power, after which the utilities remained in a constrained operating mode. Dragos reports that the loss of automated control lasted about a year or longer in some locations.32

The distinction between restoration and normal operation matters when specifying manual fallback. Returning service answers a question about what can be delivered now. Continuing under constrained supervision answers another question about what the operators can see, change and coordinate through subsequent shifts. A plan should name the local indications and communications needed to manage that second period, as well as how the control room will recognize when the fallback can no longer support safe operation.56

Automated switching capability: Ukraine, 2016

The NATO Cooperative Cyber Defence Centre of Excellence’s International Cyber Law Toolkit describes the December 17–18 outage involving the Pivnichna transmission substation near Kyiv. It records an outage of more than an hour affecting part of the city and surrounding area and reports an estimate that the lost power was equivalent to about one-fifth of Kyiv’s consumption at the time. ESET assessed that Industroyer was likely used in the incident. A U.S. indictment alleges that members of the same Russian military intelligence unit were responsible for the December 2015 and December 2016 grid attacks.4920

ESET identified four protocol payloads in the analyzed malware: IEC 60870-5-101, IEC 60870-5-104, IEC 61850 and OLE for Process Control Data Access (OPC DA). The malware could issue industrial control commands, and the samples included an activation timestamp for December 17, 2016. Researchers also found a wiper and a component intended to deny service to affected Siemens SIPROTEC devices. The associated CVE-2015-5374 describes a denial-of-service condition. The initial access path, precise execution duration and incident-specific use of optional modules remain unverified. The protocol payloads describe what the sample could do.921

Dragos modeled a response in which operators might sever communications to regain control locally if malicious switching continued. This was an analysis of a scenario. Its relevance for islanding is conditional: if malicious code already has the access it needs inside OT, cutting a link to the enterprise may leave the activity inside that boundary unaffected. A degraded-mode plan needs a way to check the local control environment and a fallback for cases in which operators no longer have confidence in supervisory control.25

Uneven production effects: Norsk Hydro, 2019

Hydro’s March 20 update says it isolated its plants and operations after detecting the ransomware incident and adopted manual procedures. Its division reports distinguish the scope of containment from the effects on production. Energy and Bauxite & Alumina reported normal production. Primary Metal reported normal production with a greater degree of manual operation. Extruded Solutions reported production problems and temporary stoppages at several plants after it lost access to production systems. Rolled Products also reported lost access to production systems, with limited operational effects. The release establishes variation across divisions. Plant-level network boundaries and the exact timing of individual cuts remain unverified.12

Idaho National Laboratory (INL) describes Hydro’s workforce of about 35,000 using manual workarounds for approximately three weeks for tasks normally supported by IT and OT. Nearly a month after the incident, INL reports, the majority of roughly 160 business segments still used manual operations. These figures describe work across the business. The division reports above give the available evidence about plant operation. Hydro estimates the total cost at around NOK 800 million on its incident page. Its 2020 annual report gives a range of about NOK 800 million to NOK 1 billion, with lost sales the primary impact and remediation costs also included.13122223

Microsoft’s account attributes to investigators the finding that a legitimate email conversation contained an attachment weaponized in December 2018. INL dates likely execution of the infected attachment to two to three weeks before the ransomware triggered in March 2019. The attachment date and estimated execution date describe separate events. The date of the initial foothold remains uncertain. Jim Moeller, a member of Microsoft’s Detection and Response Team who assembled a response team in Hungary, said the attackers distributed the ransomware manually through Hydro’s domain controllers after gaining administrative control. Hydro corporate information security officer Torstein Gimnes Are told Microsoft that paying might yield a decryption key, but the company still had to rebuild its infrastructure and remove the attacker’s access. That was his stated rationale for refusing to pay.2413

An accidentally isolated recovery asset: Maersk, 2017

NotPetya disrupted Maersk’s transport and logistics operations on June 27, 2017. WIRED reports that Maersk disconnected parts of its network during the response and that terminal staff used workarounds including paper and ordinary messaging tools to keep some cargo moving. Its reconstruction describes the loss of domain controllers and the discovery of a surviving controller at an office in Ghana. A power outage had knocked that controller offline before the attack, and the copy of directory data it held helped Maersk rebuild. The surviving controller is an example of recovery from a disconnected asset. The manual terminal workarounds separately illustrate continued service at reduced capacity.1011

Via WIRED, Maersk chairman Jim Hagemann Snabe reported a ten-day rebuild of a network of about 4,000 servers and 45,000 PCs and estimated that total shipping volume fell by about 20 percent during the outage. WIRED describes additional recovery work beyond the initial rebuild. Maersk’s annual report estimates an impact of $250–300 million, including lost revenue, IT restoration costs and extraordinary operating costs. This is a broad loss estimate. The financial and recovery figures cover different aspects of the disruption.1011

The U.S. indictment describes an apparent $300 ransom demand with no functional means to recover files through payment. In announcing the charges, Assistant Attorney General John Demers described at least hundreds of victims and nearly $1 billion in losses for three U.S.-related victims, as alleged. The financial scope is especially important when discussing ransomware decisions: recovering files, reestablishing operational trust and returning a service to its normal capacity are separate recovery objectives.2025

Unidirectional gateways and data diodes

What the hardware enforces

A hardware data diode enforces one direction over a specific link. In a strictly outbound arrangement, the hardware can carry data from the OT side to a receiving system while preventing reverse transmission across that link. NIST describes a unidirectional gateway as a combination of such hardware and software that replicates data and emulates the services that consumers expect. The software can present a copy of a historian to enterprise users without allowing their queries to reach the original historian. The receiving replica depends on what is forwarded and can be stale or incomplete. Users making operational decisions need a way to check its freshness and coverage.526

NIST gives the example of an appropriately placed one-way gateway between Layers 2 and 3 protecting lower layers against some events at higher layers. For the compression facility case, the defensive counterfactual is limited to the path that the one-way link would replace. CISA reports the phishing link as the route into IT and the pivot as a subsequent event. A strictly outbound gateway blocks reverse traffic on its own link while the risk from other routes depends on their design. Remote support, management, a maintenance bypass, update workflows and movement of equipment all require separate assessment. Forward data remains an input that the receiver must handle safely. Where firewall policies govern a conduit, NIST advises considering rules as stringent for outbound as for inbound traffic.56

Waterfall describes its hardware-enforced gateway and a separately configurable FLIP product that can reverse transfer direction manually or on a schedule. Owl emphasizes one-way enforcement in its send and receive hardware. The WF-600 revision F certificate records Common Criteria EAL4 augmented with AVA_VAN.5, ALC_DVS.2 and ALC_FLR.2. Its assurance applies to the evaluated product configuration in conjunction with the certification report. That evaluation boundary is narrower than the OT system that uses the product. Check the actual traffic paths and failover arrangements of the deployment, including what can cross while a reversible link runs in the opposite direction or when both links in a paired configuration are available.2627285

Compare by direction, availability and failure consequence

For export-only telemetry, make the local system authoritative. Agree on an acceptable age for the last sample, what a missing series looks like on the receiving dashboard, and who investigates stale data. An interrupted export may be tolerable for a report that can be regenerated from retained records. If a remote office needs live readings to coordinate with the plant, ask how it will confirm local conditions when the feed is delayed or unavailable. Specify who supervises the export service, and test whether the plant remains safe when the receiver, its software or the outbound connection is down. These are application requirements regardless of whether the consumer runs on premises or in a cloud service.5626

Interactive remote support has a different requirement. A remote specialist who must act on a controller and observe the result needs a return path. A supervised bidirectional session can meet that need where a strictly outbound telemetry link cannot. The operator should decide when the session may be opened, who must supervise it, how the plant handles loss of the session mid-task, and whether qualified local staff can substitute during isolation. A reversible or paired path also needs explicit controls for the traffic it permits. If a fallback makes the work feasible locally, removing remote support during the incident can be part of the mode. If stopping is the safe choice when the specialist is unavailable, include that condition in the plan.5266

Standards, guidance and reporting obligations

IEC 62443-3-2 covers security risk assessment for system design, including partitioning the system under consideration into zones and conduits and setting target security levels for both. IEC 62443-3-3 defines technical system security requirements and capability security levels. IEC 62443-2-1 covers security program requirements for asset owners. An operator can use the zone and conduit analysis to record which conduits are candidates for emergency isolation and what functions depend on them. That use is an engineering recommendation of this article.293031

NIST SP 800-82 Revision 3, issued in September 2023, is final. NIST released Revision 4 as an initial public draft on September 21, 2026. Revision 3 recommends considering how segmentation and isolation affect ordinary operations, safety and response. In its discussion of fail-safe design, it advises defining thresholds for operating with disrupted capabilities such as loss of network communications. The boundary design and the proposed safe state therefore need to be reviewed together.532

CISA’s compression facility advisory recommends planning for loss or manipulation of view and control and for loss of safety, with explicit criteria for deciding when to shut down and when to continue. It calls for exercising alternate controls, including manual operation with degraded electronic communications, and giving staff decision-making experience through tabletop scenarios involving lost visibility and control. It recommends capturing lessons in emergency playbooks. Separately, it observes that the victim’s emergency plan focused on physical safety threats and that its exercises did not give employees experience making decisions during a cyberattack. CISA’s tabletop catalog includes industrial control system compromise and ransomware scenarios.633

TSA’s first post-Colonial pipeline directive was issued on May 27, 2021, and GAO dates its effective start to May 28. CRS says it required a designated cybersecurity coordinator, incident reports to CISA within twelve hours, and a report of vulnerability assessment results within thirty days. GAO documents a later increase in the reporting window from twelve to twenty-four hours. TSA’s publicly available SD-01E applies to owners and operators notified by TSA that their pipeline system or facility is critical and lists an expiration date of May 2, 2026. The current reporting window is unverified here. Use the applicable obligation in a site exercise. TSA also issued a second directive requiring, among other measures, cybersecurity contingency and recovery planning for covered operators.83435

Planning the cut

Inventory the dependencies and pre-engineer the cut points

Start with the communications and the functions that depend on them. Draw the proposed boundary for each mode. For each conduit, record who starts the exchange, what direction it runs, when the data or service is needed, how operators detect loss, and how long they can tolerate it. Walk through shift change and a local restart as well as a stable shift. A console that survives an isolation exercise while already logged in may leave an authentication dependency untested. Check how a cold-started station gets credentials, where local alarms are displayed, and whether a qualified replacement operator can obtain the same view. Include the process for taking over if either a central console or an inter-site communications service is lost.56

Associate each designated cut point with the service it interrupts, its required position for the selected mode and the means to confirm that position. Record who orders the change, who applies it and who checks that the boundary is behaving as expected. Consistent with the definition above, a hardware-enforced outbound-only link may continue exporting telemetry if the response plan explicitly approves that flow and its one-way behaviour is verified during the cut. Confirm the status of every other conduit, including any management, update and support paths. Assess whether information from the receiving replica is still adequate for its intended use. Know which indications the local operator can check independently when an enterprise dashboard is stale or unavailable.5

Define a degraded operating mode

Consider a hypothetical fuels terminal whose local process can operate within a reduced envelope with enterprise links cut. The example’s assumptions belong to this terminal alone. Its minimum local services are loading control, independent safety functions, local alarm and instrument displays, local credentials and timekeeping, and records sufficient to reconcile loads against paper manifests. One qualified operator stays at the controls and another checks field indications and manifests on each shift. A qualified engineer is on call. The shift supervisor authorizes degraded loading after verifying local indications, safety functions, staffing and available inventory. The plan allows up to 72 hours subject to a shorter limit set by tankage or qualified shift coverage.56

The site pauses loading if the controls and independent field indications disagree, the inventory and manifest records cannot be reconciled within site limits, or product quality leaves its approved range. Loss of a required safety function, loss of essential operator view or expiry of staffing or inventory limits requires the planned controlled stop, using the site’s approved procedure. These criteria give operators an affirmative basis to continue and a defined decision when a prerequisite fails. During a test the supervisor checks that decisions are possible using the sources and people that will actually be present after the cut.56

Decide when reconnection is warranted

For the example terminal, the incident lead documents the affected systems, the span of trustworthy logs and remaining visibility gaps. OT engineers compare relevant controller and workstation configurations with approved baselines, restore affected services from verified recovery media as appropriate, and confirm that control, alarms and safety functions are available. They check that a local stop remains possible. The operations manager authorizes reconnection after reviewing that scoped evidence with the incident lead and the process safety lead. The team restores one approved conduit at a time, monitors for abnormal traffic and erroneous process indications, and retains the means to return to the agreed fallback. Reconnection is an operational decision with recorded conditions and residual uncertainty. Startup after a shutdown also requires its own process safety checks.56

Rehearsing islanding

Begin with a tabletop. Have the participants choose whether to isolate and continue or shut down given a specified loss of view, control or communications. Walk through who has authority, what evidence each role needs, who reports the incident, and the applicable reporting deadline. Then test the dependencies and alternate controls in stages, using a representative test environment or an approved simulation where practical. The terminal’s exercise can test login after a restart, recognition of stale data and shift handover before testing simultaneous loss of multiple services. Record the time to reach the approved mode and whether operators can verify independent indications, communicate and perform the required work for the planned duration.3365

A live disconnection exercise requires site approval, a process safety review, entry conditions, abort criteria and an agreed fallback. For the hypothetical terminal, entry requires the right staffing, verified safety and control functions, a stable process and coordination with affected delivery and support teams. A failed local indication or threatened safety margin ends the exercise under the pre-agreed fallback, which may be a controlled shutdown. Where loss of communications calls for a safe shutdown, demonstrate the transition to that state and the ability to maintain it. Measure against the site’s approved thresholds and staffing envelope. Record the observed limits and reflect them in the operating plan.56

What the case evidence can establish

The cases illustrate site-specific consequences. Colonial gives an example of standing stop-work authority exercised under uncertainty. Hydro shows why continuity must be assessed by function and facility. Maersk illustrates the value of a recovery copy outside the affected network and of viable workarounds for some services. These reports provide no comparative measure of expected return on preparation, no basis for assigning recovery costs to the decision to isolate, and no evidence that isolation determined who would pay a ransom. The sources also leave the operators’ degree of prior rehearsal uncertain.1412221011

An operator can make the actual choice more tractable by estimating the consequences of each safe mode at the site. Continued local operation incurs staffing, coordination and verification work. Shutdown requires the site to reach and hold its safe state, and may affect connected facilities or customers. Under time pressure, the practical question is how much independent information the decision maker can obtain and how much process assurance it supplies. Specify the observations that justify either mode, the conditions that would invalidate the choice and the uncertainty that the responsible manager will accept.56

Conclusion

A cut is viable when the operator can demonstrate that local control, protective functions, dependencies and staffing support the proposed mode for a specified time. Use a safety-reviewed, staged exercise to demonstrate what operators can observe and control, when they must stop, and what evidence and authority they need to reconnect. A controlled shutdown is an intended outcome wherever the safety case calls for it. The five cases distinguish preventive shutdown, manual restoration, malware capability inside a control environment, uneven production continuity and recovery from an accidentally disconnected asset. They leave the comparative costs of preparation and the effect of prior rehearsal uncertain. The operator’s decision rests on the evidence available for the process and the uncertainty the site can accept.

Footnotes

  1. Supplemental Information for New York State Standardized Interconnection Requirements, §3.1.1, National Renewable Energy Laboratory (Michael Ingram, David Narang, Barry Mather and Benjamin Kroposki), October 2017. https://docs.nlr.gov/docs/fy18osti/70183.pdf (opens in a new tab) ↩
  2. CRASHOVERRIDE: Analyzing the Threat to Electric Grid Operations, Dragos Inc., June 12, 2017. https://nsarchive.gwu.edu/sites/default/files/documents/3869008/Dragos-CRASHOVERRIDE-Analyzing-the-Threat-to.pdf (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5
  3. Analysis of the Cyber Attack on the Ukrainian Power Grid — Defense Use Case, E-ISAC and SANS ICS (Robert M. Lee, Michael J. Assante, Tim Conway), March 18, 2016. https://media.kasperskycontenthub.com/wp-content/uploads/sites/80/2016/05/21075832/E-ISAC_SANS_Ukraine_DUC_5.pdf (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5 ↩6 ↩7
  4. Industroyer – Crash Override (2016), NATO CCDCOE International Cyber Law Toolkit. https://cyberlaw.ccdcoe.org/wiki/Industroyer_%E2%80%93_Crash_Override_%282016%29 (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5
  5. Guide to Operational Technology (OT) Security, NIST Special Publication 800-82 Revision 3, September 2023. https://nvlpubs.nist.gov/nistpubs/SpecialPublications/NIST.SP.800-82r3.pdf (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5 ↩6 ↩7 ↩8 ↩9 ↩10 ↩11 ↩12 ↩13 ↩14 ↩15 ↩16 ↩17 ↩18 ↩19
  6. Ransomware Impacting Pipeline Operations, CISA Alert AA20-049A, February 18, 2020 (revised October 2020). https://www.cisa.gov/news-events/cybersecurity-advisories/aa20-049a (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5 ↩6 ↩7 ↩8 ↩9 ↩10 ↩11 ↩12 ↩13 ↩14
  7. A Reference Model for Computer Integrated Manufacturing (CIM): A Description from the Viewpoint of Industrial Automation, CIM Reference Model Committee, International Purdue Workshop on Industrial Computer Systems, edited by Theodore J. Williams, Instrument Society of America, 1989. https://www.pera.net/Pera/PurdueReferenceModel/TOC%26Intro.pdf (opens in a new tab) ↩
  8. Pipeline Cybersecurity: Federal Programs, Congressional Research Service report R46903 (Paul W. Parfomak and Chris Jaikaran), September 9, 2021. https://www.everycrsreport.com/reports/R46903.html (opens in a new tab) ↩1 ↩2
  9. Industroyer: Biggest threat to industrial control systems since Stuxnet, ESET WeLiveSecurity (Robert Lipovsky and Anton Cherepanov), June 12, 2017. https://www.welivesecurity.com/2017/06/12/industroyer-biggest-threat-industrial-control-systems-since-stuxnet/ (opens in a new tab) ↩1 ↩2 ↩3
  10. The Untold Story of NotPetya, the Most Devastating Cyberattack in History, WIRED (Andy Greenberg), August 22, 2018. https://www.wired.com/story/notpetya-cyberattack-ukraine-russia-code-crashed-the-world/ (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5 ↩6
  11. A.P. Møller-Maersk annual report on the 2017 financial year (NotPetya impact), A.P. Møller-Maersk. https://investor.maersk.com/static-files/42159a0b-a2e7-4386-988d-3d3e40f864e6 (opens in a new tab) ↩1 ↩2 ↩3 ↩4
  12. Update on the cyber attack on Hydro, Norsk Hydro press release, March 20, 2019. https://www.hydro.com/en/global/media/news/2019/update-on-the-cyber-attack-on-hydro/ (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5 ↩6
  13. Precursor Analysis Report: LockerGoga Ransomware Attack on Norsk Hydro 2019, Cybersecurity for the Operational Technology Environment (CyOTE), Idaho National Laboratory, INL/RPT-22-69758, September 30, 2022. https://cyote.inl.gov/content/uploads/24/2025/12/CyOTE-Case-Study_Norsk-Hydro.pdf (opens in a new tab) ↩1 ↩2 ↩3
  14. Written Testimony of Joseph Blount, Jr., President and CEO, Colonial Pipeline Company, U.S. Senate Committee on Homeland Security and Governmental Affairs, June 8, 2021. https://www.hsgac.senate.gov/wp-content/uploads/imo/media/doc/Testimony-Blount-2021-06-08.pdf (opens in a new tab) ↩1 ↩2 ↩3 ↩4 ↩5
  15. Media Statement Update: Colonial Pipeline System Disruption, Colonial Pipeline Company, May 8–17, 2021. https://www.colpipe.com/news-insights/media-resources/post/media-statement-update-colonial-pipeline-system-disruption/ (opens in a new tab) ↩1 ↩2
  16. Colonial Pipeline: US recovers most of ransom, justice department says, BBC News, June 8, 2021. https://www.bbc.com/news/business-57394041 (opens in a new tab) ↩1 ↩2
  17. Examining the Colonial Pipeline Cyber Attack, hearing before the U.S. Senate Committee on Homeland Security and Governmental Affairs, June 8, 2021 (oral testimony of Joseph Blount, Jr.). https://www.govinfo.gov/content/pkg/CHRG-117shrg46569/html/CHRG-117shrg46569.htm (opens in a new tab) ↩
  18. Colonial Pipeline Cyberattack Highlights Need for Better Federal and Private-Sector Preparedness, U.S. Government Accountability Office WatchBlog, May 18, 2021. https://www.gao.gov/blog/colonial-pipeline-cyberattack-highlights-need-better-federal-and-private-sector-preparedness-infographic (opens in a new tab) ↩
  19. Department of Justice Seizes $2.3 Million in Cryptocurrency Paid to the Ransomware Extortionists Darkside, U.S. Department of Justice, June 7, 2021. https://www.justice.gov/archives/opa/pr/department-justice-seizes-23-million-cryptocurrency-paid-ransomware-extortionists-darkside (opens in a new tab) ↩
  20. United States v. Andrienko et al., indictment, U.S. District Court for the Western District of Pennsylvania, filed October 15, 2020. https://www.justice.gov/archives/opa/press-release/file/1328521/dl?inline= (opens in a new tab) ↩1 ↩2
  21. CVE-2015-5374, NIST National Vulnerability Database. https://nvd.nist.gov/vuln/detail/cve-2015-5374 (opens in a new tab) ↩
  22. The cyber attack on Hydro, Norsk Hydro (updated May 15, 2024). https://www.hydro.com/en/global/media/on-the-agenda/cyber-attack/ (opens in a new tab) ↩1 ↩2
  23. Annual Report 2020, consolidated financial statements, Norsk Hydro. https://www.hydro.com/Document/Index?id=568502&name=Annual+report+2020+NEW.pdf (opens in a new tab) ↩
  24. Hackers hit Norsk Hydro with ransomware. The company responded with transparency, Microsoft (Bill Briggs), December 16, 2019. https://news.microsoft.com/source/features/digital-transformation/hackers-hit-norsk-hydro-ransomware-company-responded-transparency/ (opens in a new tab) ↩
  25. Remarks by Assistant Attorney General for National Security John C. Demers on the announcement of charges against Russian military intelligence officers, U.S. Department of Justice, October 19, 2020. https://www.justice.gov/archives/opa/speech/remarks-assistant-attorney-general-national-security-john-c-demers-announcement-charges (opens in a new tab) ↩
  26. Unidirectional Security Gateways, Waterfall Security Solutions, accessed November 25, 2026. https://waterfall-security.com/technology-and-products/unidirectional-security-gateways/ (opens in a new tab) ↩1 ↩2 ↩3 ↩4
  27. Why Data Diodes Are Critical to Modern Critical Infrastructure Security, Owl Cyber Defense, July 8, 2025. https://owlcyberdefense.com/blog/what-is-data-diode-technology-how-does-it-work/ (opens in a new tab) ↩
  28. NSCIB-CC-2400089-01 certificate for WF-600 Waterfall-Security Unidirectional Security Gateway, revision F, TrustCB, May 29, 2025. https://www.commoncriteriaportal.org/nfs/ccpfiles/files/epfiles/NSCIB-CC-2400089-01-Cert.pdf (opens in a new tab) ↩
  29. IEC 62443-3-2:2020 — Security for industrial automation and control systems, Part 3-2: Security risk assessment for system design, IEC, June 24, 2020. https://webstore.iec.ch/en/publication/30727 (opens in a new tab) ↩
  30. IEC 62443-3-3:2013 — Industrial communication networks, network and system security, Part 3-3: System security requirements and security levels, IEC, August 7, 2013. https://webstore.iec.ch/en/publication/7033 (opens in a new tab) ↩
  31. IEC 62443-2-1:2024 — Security for industrial automation and control systems, Part 2-1: Security program requirements for IACS asset owners, IEC, August 7, 2024. https://webstore.iec.ch/en/publication/62883 (opens in a new tab) ↩
  32. NIST Special Publication 800-82 Revision 4, Initial Public Draft, NIST, September 21, 2026. https://csrc.nist.gov/pubs/sp/800/82/r4/ipd (opens in a new tab) ↩
  33. CISA Tabletop Exercise Packages, Cybersecurity and Infrastructure Security Agency, accessed November 25, 2026. https://www.cisa.gov/resources-tools/services/cisa-tabletop-exercise-packages (opens in a new tab) ↩1 ↩2
  34. Surface Transportation: TSA Is Taking Steps to Enhance Cybersecurity, but Additional Actions Are Needed, U.S. Government Accountability Office report GAO-25-107947, 2025. https://files.gao.gov/reports/GAO-25-107947/index.html (opens in a new tab) ↩
  35. Security Directive Pipeline-2021-01E: Enhancing Pipeline Cybersecurity, Transportation Security Administration, effective May 3, 2025. https://www.tsa.gov/sites/default/files/tsa-security-directive-pipeline-2021-01e-and-memo-508c.pdf (opens in a new tab) ↩